MV CABLENA2XSY cable construction cutaway
iNKA CableCatalog product illustration

MEDIUM VOLTAGE · TECHNICAL DATASHEET

NA2XSY

YAXC7V-R

XLPE-insulated aluminium medium-voltage cable with a copper screen and PVC outer sheath.

Rated voltage
6/10 kV
Conductor
Aluminium
Insulation
XLPE

From the iNKA MV catalog · 4 product sheets

SELECT YOUR CABLE

Sizes, dimensions & ratings

Choose a configuration and cable size to view its dimensions, weight and published electrical characteristics.

11 sizes · 6/10 kV

NA2XSY · 6/10 kV
Cable sizeNominal cross-sectionOuter diameter, approximatelymmCable weight, approximatelykg/kmCable length, approximatelymConductor DC resistance at 20 °CΩ/kmCapacitanceµF/kmCurrent in ground at 20 °C (flat)ACurrent in air at 30 °C (flat)A
22,053010001,200,19——
23,057510000,8680,21155170
24,063510000,6410,23194215
26,072510000,4430,26236269
28,083010000,3200,30281327
29,093010000,2530,32318377
30,0112510000,2060,35350424
32,0126510000,1640,38393485
34,0148510000,1250,43453573
37,0171010000,1000,47507652
40,0212010000,07780,52559741

Select a size to focus on its specifications. Scroll horizontally to see every column.

  • Dimensions, weight and cable length are approximate as published. Current ratings use the catalog’s flat arrangement, ground temperature 20 °C and air temperature 30 °C.
  • — indicates a value not specified in this catalog table.
View original catalog table
1 / 4
Full size
Original iNKA NA2XSY technical table, 6/10 kV, PDF page 54
iNKA MV catalog · page 54View original page

PRODUCT OVERVIEW

Application

For power centres, switchgear, industrial facilities and local energy distribution; installed indoors, outdoors, underground or in cable ducts where there is no risk of mechanical damage.

Standards listed in the catalog

  • TS IEC 60502-2
  • IEC 60502-2
  • TS HD 620 S2
  • HD 620 S2

SPECIFICATIONS

Electrical & mechanical data

6/10 kV
Conductor material
Aluminium
Insulation
XLPE
Outer sheath
PVC
Number of cores
1
Max. operating temperature
90 °C
Max. short-circuit temperature
250 °C for 5 seconds
Minimum bending radius
15 × cable outer diameter (D)
Maximum tensile stress
30 N/mm²
Conductor class
Class 2 according to IEC 60228
Conductor construction
Circular compacted aluminium
Outer sheath compound
PVC / ST2 (IEC 60502-2)
Minimum cable-laying temperature
−5 °C (general catalog guidance; see cold-laying note)
Rated voltage U₀/U
6/10 kV

D = cable outer diameter. Refer to the stated conditions for each specification.

LAYERS & MATERIALS

Cable construction

NA2XSY layers and conductor cutaway
  1. Circular compacted aluminium conductor, Class 2 (IEC 60228)
  2. Extruded semi-conductive conductor screen
  3. XLPE insulation
  4. Extruded bonded semi-conductive insulation screen
  5. Semi-conductive tape
  6. Copper wire and tape screen
  7. PE tape
  8. PVC outer sheath

Construction & performance notes

  • Single-core construction
  • XLPE insulation
  • Bonded semi-conductive insulation screen
  • Copper wire and tape screen
  • PVC outer sheath